Threshold converter type M2218
No stock. Please contact us for more information!
The threshold converter M2218 is used to check or control either a signal current or a temperature. A Pt-100 platinum sensor in 3-wire mode can be connected to the unit. It converts the input signal to an internal standard signal of 0 to 100.0%. Two independent limit contacts can be set within this range.
- Input M2218-A: 4...20mA
- Input M2218-T: Pt-100 0...160ºC
- 2 alarm contacts
- programmable
Data Sheet
Certificate
Leaflet
Software to configure and program the M2218 series.
Product Details: Threshold converter type M2218
The threshold converter M2218 is used to check or control either a signal current or a temperature. A Pt-100 platinum sensor in 3-wire mode can be connected to the unit. It converts the input signal to an internal standard signal of 0 to 100.0%. Two independent limit contacts can be set within this range.
All settings as limit values, hysteresis, range and operating mode of the contacts can be set with a PC-program.
The unit may be programmed to customers values or ranges by the factory.
A typical application would be to measure and monitor pressure in a process vessel:
A pressure transmitter converts the pressure of 1 to 10 bar to a current signal of 4 to 20mA. The M2218 monitors under- and overpressure in the vessel. It converts the 4...20mA signal current to 0...100.0%. The alarm is set between 0% (=1 bar) and 100.0% (=10 bar). With these floating alarm contacts, overpressure valves, compressor relays, etc. are driven directly.
If a Pt-100 sensor is connected to the input, the unit works as a temperature monitor or as a simple temperature controller.
Optionally a galvanically isolated output signal of 4...20mA is available.
The 24VDC power supply is galvanically isolated from the input circuit and the output current source.